chakei.com-一出一进一爽一粗一大视频,中文字幕一区二区三区精华液,欧美成人午夜精品久久久,欧美成人一区二区三区在线视频

M12 interface、IO-Link Hub、PNP、16DI/DO configurable、 Expandable modules、00BG11

M12 interface、IO-Link Hub、PNP、16DI/DO configurable、 Expandable modules、00BG11

Ordering code: 00BG11
Part number : FNI IOL-309-002-M12
  • IO-Link M12集線器 16×DI PNP(圖1)
  • >IO-Link device
  • >8 ports and 16 signals
  • >Input/Output adaptation
  • >Protection level: IP 67 (when correctly connected)
Inquires 詢盤

Related recommendations

  • Function Parameter
  • Resource Download
  • Related accessories
IO-LinkDevice
IllustrateExpandable modules
Type16×DI/DO PNP
Rated working voltage UB18...30 V
IO-Link RUN enegry indication lightGreen LED indicator light
Power start-up indication lightGreen LED indicator light
Connection: IO-Link M12,A-coded,Male/ D-coded,Male
Connection: I/O portM12,A-coded,F(xiàn)emale
Connection: UOVia IO-Link interface
Connection: UAVia IO-Link interface
Number of I/O ports8
Input quantityMaximum 16
Output quantityMaximum 16
Configurable/parameterizedYes
Single channel monitoringNo
Codable via IO-LinkNo
Maximum load current,sensor/channel100 mA
Maximum load current actuator0.5A
Port status indicatorYellow/Red LED
Total current UT< 1.4A
Total current UO< 1.4A
Degree of protection as per IEC 60529IP67(When connected correctly)
Operating temperature-25...+70 ℃
Storage temperature-25...+85 °C
Weight-
Fastener2 pcs mounting hole
Dimensions (length × width × height)153.4×65×29 mm
Shell materialZinc alloy
RemarkIt is recommended to use 64DD61-xxx together (see 2.2.33)
lO-Link 1.1
Max. cycle time5 ms
IO-Link tackled data length4 pcs input bytes/4 pcs outputs bytes
Indicator light communicationGreen LED indicator light
Indicator light errorRed LED indicator light